ATTENTION: The works hosted here are being migrated to a new repository that will consolidate resources, improve discoverability, and better show UTA's research impact on the global community. We will update authors as the migration progresses. Please see MavMatrix for more information.
Show simple item record
dc.contributor.advisor | Agonafer, Dereje | |
dc.contributor.advisor | Kumar, Ratan | |
dc.creator | Adsul, Kaustubh Kantilal | |
dc.date.accessioned | 2022-07-14T16:51:17Z | |
dc.date.available | 2022-07-14T16:51:17Z | |
dc.date.created | 2021-05 | |
dc.date.issued | 2021-05-18 | |
dc.date.submitted | May 2021 | |
dc.identifier.uri | http://hdl.handle.net/10106/30705 | |
dc.description.abstract | Direct-to-chip liquid cooling is one of the most popular methods in data center thermal management when it comes to cooling high chip power densities. A cold plate-based liquid cooling system contains various components such as pumps, data center room, and rack-level manifolds, and server chassis-level manifold. Efficient coolant distribution to the heat-dissipating cold plates plays an important role in both the thermal and hydraulic performance of the server. It is, thus, very important to design and manufacture server chassis manifold geometry that can perform efficiently under the anticipated heat loads and coolant flow rates. In the present thesis, two such server chassis manifolds from two different vendors were characterized using CFD for various coolant inlet temperatures and flow rates. A gird independence study was carried out to select the best possible grid size for accurate results. Temperature-dependent properties of 25% propylene glycol were used to determine the pressure drops at different flow rates and inlet temperatures. The baseline results of manifold pressure drop were also validated with experimental results. Furthermore, the impact of kinks and bends in server manifold connecting pipes on the system pressure drop was also explored. Lastly, the fillet was added on the corners of manifold to see the difference between the pressure drop. | |
dc.format.mimetype | application/pdf | |
dc.language.iso | en_US | |
dc.subject | CFD | |
dc.subject | Propylene glycol | |
dc.subject | Server manifold | |
dc.subject | Manifol | |
dc.subject | Data center | |
dc.subject | Cold plates | |
dc.subject | Pressure drop | |
dc.subject | Temperature | |
dc.subject | Grid independence | |
dc.title | THERMAL DESIGN ANALYSIS OF SERVER CHASSIS MANIFOLDS FOR LIQUID COOLED SERVERS USING CFD | |
dc.type | Thesis | |
dc.degree.department | Mechanical and Aerospace Engineering | |
dc.degree.name | Master of Science in Mechanical Engineering | |
dc.date.updated | 2022-07-14T16:51:17Z | |
thesis.degree.department | Mechanical and Aerospace Engineering | |
thesis.degree.grantor | The University of Texas at Arlington | |
thesis.degree.level | Masters | |
thesis.degree.name | Master of Science in Mechanical Engineering | |
dc.type.material | text | |
Files in this item
- Name:
- ADSUL-THESIS-2021.pdf
- Size:
- 1.230Mb
- Format:
- PDF
This item appears in the following Collection(s)
Show simple item record